Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Manchester Q (City of Calgary)

From FireAlarmPedia
Revision as of 23:40, 5 April 2024 by Alberta Fire Alarms (talk | contribs) (BEEP! RING!)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3X
FACP Location: Main Entrance Vestibule
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, EST
Date of last known Upgrade: circa 2014
Year Opened: Late 1970s

Manchester is a City of Calgary operations centre located at 651 25 Avenue Southeast, in Calgary, Alberta, Canada. This page will cover building Q, which is fleet services, where Calgary Transit vehicles are serviced. The building was built in the late 1970s, and the fire alarm system was upgraded around 2014.

System Specifications (2010s-present)

FACP

The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST’s Signature addressable protocol, and the system coding is temporal.

Booster Panels

There are two Edwards BPS6A 6-amp power supplies in the main entrance vestibule.

Notification Appliances

Most notification appliances are EST “Genesis” G1F-HDVM horn/strobes (white, wall-mount, FIRE marking, set to 15cd).
There are also EST G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd) in some areas.
For exterior notification, there is an EST “Integrity” 757-1A-T remote horn (red, wall-mount).
Outside the main entrance, there is an Edwards 439D-10AWC vibrating bell (10” gong) and an Edwards CS405-7A-T weatherproof remote strobe (red, 15/75cd) directly under it.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors throughout the building.
The top of the stairwell has an EST SIGA-PS addressable photoelectric smoke detectors.
All detectors are mounted on SIGA-SB bases.
There are EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detectors on the air handling unit.