System Specifications |
---|
FACP: EST QuickStart QS4 FACP Location: Main Lobby System Type: Hybrid System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes Date of last known Upgrade: 2013 Year Opened: 1919 |
The Agriculture Building is a space for animal stalling and show preparation, located in Stampede Park. It also has the Victoria Pavilion, an arena with seating for 1300 people. It also has three large pavilions, 6012 square meters combined. It was built in 1919, and is the oldest building on the stampede grounds. It underwent expansions in the 1940s, and 1957. The fire alarm system was installed in 2013, following the flood.
System Specifications (1990s/2013-present)
FACP
The building is protected by an EST QuickStart QS4 hybrid-addressable fire alarm system. The panel is located in the main lobby. The system runs EST's Signature addressable protocol, and the system coding is temporal.
Notification Appliances
Lobby
All notification appliances are EST "Genesis" G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd).
Stables
The notification appliances are a mix of Edwards 439D-6AWC vibrating bells (6" gong) and Edwards 439D-10AWC vibrating bells (10" gong).
Initiating Devices
Pull Stations
The stables have EST SIGA-270 addressable single-action pull stations.
The lobby has Tyco/Grinnell MS-401GR conventional single-action pull stations.
The offices have Edwards 274-111 conventional single-action pull stations.
Automatic Detection Devices
None noticed.