Hyatt House Tampa Airport/Westshore (West)

From FireAlarmPedia
Revision as of 17:08, 25 May 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS2-3030 w/DVC
FACP Location: Lobby
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70VRMS (audible)
24VDC (sounders & visual)
System Coding: Unknown
Strobes Synchronized: Yes, SS
Date of last known Upgrade: N/A
Year Opened: 2018

Hyatt House is a chain of hotels owned by Hyatt. This particular hotel is located at 5308 Avion Park Dr, Tampa, FL and is close to the Tampa International Airport. It is the west hotel of the two hotels of the same name. It was built in 2018, and the fire alarm system is original.

System Specifications (2018-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS2-3030 addressable fire alarm system. The panel is located in the lobby. The system runs Notifier’s FlashScan addressable protocol, and is equipped with the Digital Voice Command (DVC) voice evacuation system. The tones and/or messages are unknown.

Notification Appliances[edit | edit source]

All notification appliances are from System Sensor’s “L-Series” line of products.
Most notification appliances are System Sensor SPSCWL speaker/strobes (white, ceiling-mount, set to 30cd).
Some areas have System Sensor SPSWL speaker/strobes (white, wall-mount, set to 15cd).
Areas requiring more audible coverage have System Sensor SPWL speakers (white, wall-mount.
There are System Sensor SWL remote strobes (white, wall-mount, set to 15cd) in each guest room’s bathroom.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-951 addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B300-6 bases.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.