Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

McDonald's (Alexandra Park)

From FireAlarmPedia
System Specifications
FACP: Simplex 4010ES
FACP Location: Main Entrance Vestibule
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: N/A
Year Opened: 2016

McDonald's is a fast food restaurant chain. This particular location is located at 4809 43A Ave, Leduc, AB. It was built in 2015, and has the original fire alarm system.

System Specifications (2016-present)

FACP

The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex's IDNet addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are from Simplex's "TrueAlert" line of products. All areas except the washrooms have Simplex 4906-9127 horn/strobes (red, wall-mount, set to 15cd). The washrooms have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9004 addressable single-action pull stations.

Automatic Detection Devices

None noticed. There is a sprinkler system with waterflow detection.

Modules

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.