Stampede Station

From FireAlarmPedia
System Specifications
FACP: Siemens FireFinder XLS
FACP Location: FACP Room
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM (First Stage)
Temporal (GA)
Strobes Synchronized: Yes
Date of last known Upgrade: 2013
Year Opened: 1981

Stampede Station is an office building located at 1331 MacLeod Trail Southeast, in Calgary, Alberta, Canada. The building opened in 1981, and was redeveloped in 2013. The fire alarm system was upgraded in 2013.

System Specifications (2013-present)

FACP

The building is protected by a Siemens FireFinder XLS addressable fire alarm system. The panel is located in the FACP room on the main floor. The system runs Siemens’ FirePrint addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The first stage signal is 20BPM, followed by temporal in general alarm. The system has voice messages.

Notification Appliances

All notification appliances are Siemens CS-4100-series speaker/strobes.

Initiating Devices

Pull Stations

All pull stations are Siemens HMS-2S addressable 2-stage single-action pull stations.

Automatic Detection Devices

There are Siemens HFP-11 addressable multi sensor smoke/heat detectors in the stairwells and server rooms. The building is equipped with a wet sprinkler system.

Modules

There are Siemens XTRI-M addressable monitor modules supervising the sprinkler system’s tamper and flow switches.