More actions
System Specifications |
---|
FACP: Edwards EST3 FACP Location: Unknown System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: Unknown Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Year Opened: 2022 |
The ICE District Connect Centre is an entertainment/retail plaza located adjacent to Rogers Place, at 10324 103 Street NW, in Downtown Edmonton, Alberta, Canada. The plaza’s primary tenants are Loblaws City Market, Plantlife, ICE District Authentics, and The Canadian Icehouse. The building was built in 2022, and the fire alarm system is original.
System Specifications
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. This is likely a networked system; the panel locations are unknown. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the messages and/or tones are unknown at this time.
Notification Appliances
Common Areas & Most Units
Most notification appliances are Edwards “Genesis” GCF-S7VM speaker/strobes (white, ceiling-mount, FIRE marking, 70V, set to 15cd).
Some areas have Edwards G4F-S7VM speaker/strobes (white, wall-mount, FIRE marking, 70V, set to 15cd).
Plantlife has an Edwards GCSVWN speaker/strobe (white, ceiling-mount, no marking, set to 70V/15cd).
For outdoor notification, there is an Edwards “Integrity” 757-1A-SS70W remote speaker (white, wall-mount, 70V) paired with an Edwards CS405-7A-T weatherproof remote strobe (red, wall-mount, 15/75cd).
ICE District Authentics
This unit has a mix of Edwards “Genesis” G4SVWF speaker/strobes (white, wall-mount, FIRE marking, set to 70V/15cd) and Edwards GCSVWF speaker/strobes (white, ceiling-mount, FIRE marking, set to 70V/15cd).
Pedway
All areas of the pedway have Edwards “Genesis” GCSVWF speaker/strobes (white, ceiling-mount, FIRE marking, set to 70V/15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Edwards SIGA-OSD addressable optical smoke detectors in most areas, mounted on Edwards SIGA-SB bases.
Modules
There are EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all signal and sprinkler circuits.