FACP: Simplex 4100ES FACP Location: Main Entrance System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: Unknown Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: 2020 Year Opened: 1967 |
Stanley A. Milner Library is a library located at 7 Sir Winston Churchill Square, in Downtown Edmonton, Alberta, Canada. The library is owned and operated by the Edmonton Public Library. The library was built in 1967, and extensively renovated in 2020. The fire alarm system was upgraded as part of the 2020 renovation.
System Specifications (2020-present)
FACP
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the messages and/or tones are unknown at this time.
Notification Appliances
Most notification appliances are Simplex “TrueAlert” 4906-9154 speaker/strobes (white, ceiling-mount, set to 70V/15cd).
Some areas have Simplex 4902-9721 remote speakers (white, ceiling-mount, set to 70V).
Areas with open ceilings have Simplex 4906-9153 speaker/strobes (white, wall-mount, set to 70V/15cd).
The second floor has Simplex 4906-9104 remote strobes (white, ceiling-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on all SLCs.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all signal and sprinkler circuits.