Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Best Western Sunrise Inn & Suites

From FireAlarmPedia
Revision as of 13:06, 22 June 2024 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FX-2000 <br />FACP Location: Unknown <br />System Type: Addressable <br />Syst...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FX-2000
FACP Location: Unknown
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: N/A
Year Opened: 2008

Best Western is a hotel chain headquartered in Phoenix, Arizona, USA. This particular hotel is located at 3001 43rd Avenue, in Stony Plain, Alberta, Canada. The hotel opened in 2008, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is likely located in the administration area. The system runs Mircom’s CLIP addressable protocol, and the system coding is temporal.

Annunciators

There is a Mircom RAX-LCD annunciator in the main entrance vestibule.

Notification Appliances

All common areas have Mircom “Select-A-Horn/Strobe” FHS-240R horn/strobes (red, wall-mount, 15cd).
All guest rooms have Mircom MH-S25WA silenceable mini-horns (white, wall-mount) paired with Mircom FS-240W remote strobes (white, wall-mount, set to 110cd).

Initiating Devices

Pull Stations

Most pull stations are Mircom MS-401AD addressable single-action pull stations.
Some areas have Mircom MS-401AP addressable single-action pull stations as deficiency replacements.

Automatic Detection Devices

There are Mircom MIX-2251BA addressable photoelectric smoke detectors throughout all corridors and in all guest rooms, mounted on System Sensor B710LPA bases.

Modules

There are Mircom MIX-M500DMA addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Mircom MIX-M500RA addressable relay modules serving various purposes.

EOLs

There are Mircom MP-300 end of line resistor plates on all common area and suite strobe signaling circuits, and on all sprinkler circuits.