System Specifications |
---|
FACP: Simplex 4100U FACP Location: Main Entrance System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: 2010 Year Opened: 1973 |
The Calgary Fire Department is the fire department serving The City of Calgary. This page will cover Station 1, located at 450 1 Street SE, in Calgary, Alberta, Canada. The station opened in 1973, and the fire alarm system was upgraded in 2010.
System Specifications (2010-present)
FACP
The building is protected by a Simplex 4100U addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
Notification Appliances
All indoor notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a Simplex 4906-9105 weatherproof remote strobe (red, wall-mount, set to 15cd) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the second floor, at the top of each stairwell, and in all living quarters and offices.
There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors throughout all other areas.
All detectors are mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9002 addressable relay modules for HVAC shutdown.
There are Simplex 4090-9116 addressable isolator modules on the SLC.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all signal circuits.