System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2012 |
The Airdrie Fire Department is the fire department serving The City of Airdrie. This page will cover the headquarters building/Chinook Winds Station, located at 2525 Chinook Winds Drive SW, in Airdrie, Alberta, Canada. The building was built in 2012, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Annunciators
There is a Notifier LCD2-80 annunciator paired with a Notifier ACM-24AT annunciator in the west entrance vestibule.
Booster Panels
There is a Notifier FCPS-24S8C booster power supply next to the main FACP.
Notification Appliances
All notification appliances are System Sensor “SpectrAlert Advance” P4RA horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout most areas.
The elevator shaft has a Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detector.
All aforementioned detectors are mounted on System Sensor B710LPA bases.
There is a System Sensor DNRA duct smoke detector with a Notifier FSP-851A addressable photoelectric head on the main HVAC unit.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.