System Specifications
FACP: Simplex 4010
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: N/A
Year Opened: 2009

The Calgary Fire Department is the fire department serving The City of Calgary. This page will cover Station 35, located at 11280 Valley Ridge Boulevard NW, in Calgary, Alberta, Canada. The station was built in 2009, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4010 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the second floor and in all stairwells.
There is a Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detector in the main electrical room.
All aforementioned detectors are mounted on Simplex 4098-9792 bases.
There are Simplex 4098-9755 addressable photoelectric duct smoke detectors on all air handling units.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.