System Specifications
FACP: Notifier AFP-200
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 1995
Year Opened: 1987

Sobeys is a Canadian grocery store chain headquartered in Stellarton, Nova Scotia. This particular store is located at 392 St Albert Trail, in St. Albert, Alberta, Canada. The store was built in 1987 as IGA, and was expanded in 1995. The fire alarm system was upgraded during the 1995 conversion.

System Specifications (1995-present)

Please note that this system only supervises Sobeys. The rest of the plaza does not have a fire alarm system.

FACP

The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel location is unknown. The system runs Notifier’s CLIP addressable protocol, and the system coding is continuous.

Annunciators

There is a Notifier LCD-80 annunciator in the main entrance vestibule.

Notification Appliances

All notification appliances but one are System Sensor “Multi-Alert” MASS24LOA sounder/strobes (red, ceiling-mount, 1.5cd).
There is a System Sensor “SpectrAlert Advance” P2RA horn/strobe (red, wall-mount, set to 15cd) in Aisle 7 as a deficiency replacement.

Initiating Devices

Pull Stations

All pull stations are Notifier NFM-950B conventional single-action pull stations.
All stations are wired to Notifier MMX-101A addressable monitor modules.

Automatic Detection Devices

None noticed.

Modules

There are Notifier MMX-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.