System Specifications |
---|
FACP: Notifier NFS2-3030C FACP Location: Networked, 6 nodes System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 70VRMS (audible) 24VDC (visual) System Coding: Unknown Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2012 Year Opened: 1969 |
The Ontario Science Centre is a science museum located at 770 Don Mills Rd, North York, Ontario. The facility was opened in 1969, and the fire alarm system was upgraded in 2012. The museum closed in June 2024, but is still up.
System Specifications (2012-present)
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The system is a network consisting of six panels. The system runs Notifier’s FlashScan addressable protocol, and is equipped with voice-evacuation. The system is configured for two-stage operation. The tones and/or messages are unknown at this time, but are bilingual. The system also has the ability to silence alarms in other areas.
FACP Accessories
There are two Notifier ONYXWorks workstation computers on the system.
Annunciators
There is a Notifier graphic annunciator in the lobby. There is also a Notifier ONYX FirstVision firefighters’ display with a touchscreen.
Notification Appliances
All notification appliances are from System Sensor’s “SpectrAlert Advance” line of products.
Most audible notification appliances are System Sensor SPCWA speakers (white, ceiling-mount).
Most areas also have System Sensor SRA remote strobes (red, wall-mount, set to 15/75cd).
The Telus Rainforest has System Sensor SPRKA weatherproof speakers (red, wall-mount) and System Sensor SRKA weatherproof remote strobes (red, wall-mount, set to 75cd).
There is one System Sensor “L-Series” SRLA remote strobe (red, wall-mount, set to 75cd) in the same area as a deficiency replacement.
Initiating Devices
Pull Stations
All pull stations are Secutron MRM-MPG2ID conventional two-stage pull stations. Each station is wired to two Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B210LPA bases.
There are System Sensor DNRA duct smoke detector housings with FSP-851A addressable photoelectric heads.
There are VESDA aspirating smoke detection systems in some areas.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.