Carewest Nickle House

From FireAlarmPedia
System Specifications
FACP: Notifier AFP-200
FACP Location: Main Entrance Vestibule
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, Partial Self-Sync
Date of last known Upgrade: 2000s
Year Opened: 2000

Nickle House is an adult continuing care facility operated under the Carewest marque of Alberta Health Services, the local health authority in Alberta, Canada. This particular location is located at 950 Robert Road NE in Calgary, AB. It was built in 2000, and the system is original to the building.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel is located in the front entrance vestibule. The system runs Notifier's CLIP addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal.

Annunciators[edit | edit source]

There is a Notifier LCD-80 annunciator in the nurses office.

Notification Appliances[edit | edit source]

Most notification appliances are System Sensor "SpectrAlert" P2415WA horn/strobes (white, wall-mount, 15cd/electromechanical).

There are a few System Sensor "SpectrAlert Advance" P4RA horn/strobes (red, wall-mount, set to 15cd) as deficiency replacements.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier MPS-950KB two stage pull stations, wired to two Notifier MMX-101A addressable monitor modules each.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA bases.

Waterflow Switches[edit | edit source]

There is one Potter PS10 waterflow pressure switch attached to a dry system, wired to a Notifier MMX-101A addressable monitor module.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.