Hampton Inn Huntington University Area

From FireAlarmPedia
System Specifications
FACP: EST iO500
FACP Location: Unknown
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2013

Hampton Inn is a chain of mid range hotels owned by Hilton. The chain is headquartered in McLean, VA, and has locations globally. This particular hotel is located at 177 Kinetic Dr, Huntington, WV, The hotel opened in 2013, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an EST iO500 addressable fire alarm system. The panel location is unknown. The system runs EST’s Signature addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

There are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd) throughout all common areas.
All guest rooms have Edwards G1RF-HDVM horn/strobes (red, wall-mount, FIRE marking, set to 110cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-278 addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA2-PS addressable photoelectric smoke detectors in all common areas, mounted on EST SIGA-SB4 bases.
There are EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detectors on all air handling units, with EST SIGA-LED remote indicators mounted on ceiling tiles.