System Specifications |
---|
FACP: Gamewell-FCI E3 FACP Location: Unknown System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 2023 Year Opened: 1994 |
North Clackamas Aquatic Park is a waterpark located at 7300 Southeast Harmony Road, in Milwaukie, Oregon, USA. The park opened in 1994, and the fire alarm system was upgraded in 2023.
System Specifications (2023-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Gamewell-FCI E3 addressable fire alarm system. The panel location is unknown. The system runs Gamewell’s Velocity addressable protocol, and the system coding is likely continuous.
Notification Appliances[edit | edit source]
Most notification appliances are Simplex 2901-9845 remote horns (red, wall-mount) mounted on Simplex 4904-9105 strobe plates (15cd). Areas requiring additional visual coverage have Simplex 4904-9137 remote strobes (15cd) and Wheelock LSM-24 remote strobes (15cd). Wheelock AS-24MCW-FR horn/strobes (red, wall-mount, set to 15cd) and Wheelock “Exceder” HSR horn/strobes (red, wall-mount, set to 15cd) are installed as deficiency replacements throughout.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Gamewell-FCI MS-7ASF addressable single-action pull stations.
Automatic Detection Devices[edit | edit source]
Not known.
System Specifications (1994-2023)[edit | edit source]
FACP[edit | edit source]
The building was protected by a Simplex 4002 conventional fire alarm system. The panel location was unknown. The system coding was continuous.
Notification Appliances[edit | edit source]
Most notification appliances were Simplex 2901-9845 remote horns (red, wall-mount) mounted on Simplex 4904-9105 strobe plates (15cd). Areas requiring additional visual coverage had Simplex 4904-9137 remote strobes (15cd) and Wheelock LSM-24 remote strobes (15cd). Wheelock AS-24MCW-FR horn/strobes (red, wall-mount, set to 15cd) and Wheelock “Exceder” HSR horn/strobes (red, wall-mount, set to 15cd) were installed as deficiency replacements throughout. All notification appliances are still in use on the new system.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Simplex 2099-9754 conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There were Simplex 2098-9201 conventional photoelectric smoke detectors throughout the building. Some areas had Simplex “TrueAlarm” 4098-9601 conventional photoelectric smoke detectors as deficiency replacements.