System Specifications |
---|
FACP: Mircom FX-2000 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: 2019 Year Opened: 2014 |
Flores & Pine is a restaurant located at 254028 Bearspaw Rd, Calgary, AB. The building was originally built in 2004 as Bear’s Den, which closed in 2018. In 2019, the current restaurant opened, and the fire alarm system was upgraded during those renovations.
System Specifications (2019-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Mircom’s Advanced addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, bilingual marking, set to 15cd/electromechanical).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Mircom MS-401AP addressable single-action pull stations.
Automatic Detection Devices[edit | edit source]
The dining area has Mircom MIX-2251APA addressable photoelectric smoke detectors.
The kitchen has Mircom MIX-5251RAPA addressable rate-of-rise heat detectors.
All detectors are mounted on System Sensor B210LPA bases.
Modules[edit | edit source]
There is a Mircom MIX-M500MAPA addressable monitor module supervising the kitchen suppression system.
EOLs[edit | edit source]
There are Mircom MP-300 end of line resistor plates on the kitchen suppression and signal circuits.
Former System Specifications (2004-2019)[edit | edit source]
Former System Specifications |
---|
FACP: Mircom FX-2000 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Mircom Date of last known Upgrade: N/A Year Installed: 2004 Year Decommissioned: 2019 |
FACP[edit | edit source]
The building was protected by a Mircom FX-2000 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Mircom’s CLIP addressable protocol, and the system coding was temporal.
Notification Appliances[edit | edit source]
All notification appliances were Mircom “Select-a-Horn/Strobe” FHS-240W horn/strobes (white, wall-mount, set to 15cd/electromechanical).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Mircom MS-401AD addressable single-action pull stations.
Automatic Detection Devices[edit | edit source]
There were Mircom MIX-2251B addressable photoelectric smoke detectors in the dining room.
The kitchen had Mircom MIX-5251HBA addressable 190°F fixed-temperature heat detectors.
All detectors were mounted on System Sensor B710LPA bases.
Modules[edit | edit source]
There was a Mircom MIX-M501MA addressable monitor module supervising the kitchen suppression system.