PBS Systems

From FireAlarmPedia
System Specifications
FACP: Edwards iO1000
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2020

PBS Systems is a Canadian automotive dealer engineering company. This page covers their head office, located at 4041 128 Avenue Southeast, in Calgary, Alberta, Canada. The building opened in 2020, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards iO1000 addressable fire alarm system. The panel is located in the main electrical room, which is located in the parkade. The system runs Edwards’ Signature addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is an EST RLCD-C annunciator paired with an EST RLED24 annunciator in the side entrance vestibule.

Notification Appliances[edit | edit source]

Most notification appliances are Edwards “Genesis” G1AVRF horn/strobes (red, wall-mount, set to 15cd). Some areas have Edwards GCAVWF horn/strobes (white, ceiling-mount, set to 15cd). Areas requiring additional sound coverage have Edwards G1RF-HD remote horns (red, wall-mount, FIRE marking).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Edwards SIGA-OSD addressable optical smoke detectors throughout the building, as well as Edwards SIGA-HRD 135°F fixed/rate-of-rise heat detectors in the electrical and mechanical rooms. All detectors are mounted on EST SIGA-SB bases. All aboveground floors are protected by a wet sprinkler system; the parkade is equipped with a dry sprinkler system.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. There are EST SIGA-IM isolator modules on the system.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.