City of Airdrie Chinook Winds Parks Maintenance

From FireAlarmPedia
System Specifications
FACP: Simplex 4007ES
FACP Location: Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2024
Year Opened: 2015

Chinook Winds Parks Maintenance is the unofficial name for a City of Airdrie parks maintenance facility located at 3101 Chinook Winds Drive SW, in Airdrie, Alberta, Canada. The building was built in 2015, and the fire alarm system was upgraded in 2024. Prior to 2024 there was no dedicated fire alarm system; the security system was used for fire protection.

System Specifications (2024-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located at the main entrance. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

Most notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).
Areas requiring additional visual coverage have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd).
Areas exposed to weather, including outside the main entrance, have Simplex 4906-9131 weatherproof horn/strobes (red, wall-mount).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations but one are Simplex 4099-9004 addressable single-action pull stations.
The wash bay has an RSG RMS-1T-WP weatherproof conventional single-action pull station, wired to a Simplex 4090-9001 addressable monitor module.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors at the top of each stairwell, and throughout the second floor.
All detectors are mounted on Simplex 4098-9792 bases.

Modules[edit | edit source]

There are Simplex 4090-9116 addressable isolator modules on the SLC.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all signal circuits.