Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

St. Albert Centre

From FireAlarmPedia
System Specifications
FACP: Siemens FireFinder XLS
FACP Location: Unknown
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: No
Date of last known Upgrade: 2017
Year Opened: 1980

St. Albert Centre is a shopping mall located at 375 St Albert Trail, in St. Albert, Alberta, Canada. The mall opened in 1980, and was renovated in 2017. The fire alarm system was upgraded as part of the 2017 renovation.

System Specifications (2017-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Siemens FireFinder XLS addressable fire alarm system. The panel location is unknown. The system runs Siemens’ FirePrint addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal.

Annunciators[edit | edit source]

There is a Siemens SSD-C annunciator at the entrance by London Drugs.

Notification Appliances[edit | edit source]

Most notification appliances are Wheelock MT-24-CWS horn/strobes (red, ceiling-mount, set to horn), installed in the 1990s.
Newer areas have Siemens MTH-MC-R-B horn/strobes (red, wall-mount, set to horn/15cd).
Some areas have Siemens ZH-MC-R-B horn/strobes (red, wall-mount, set to 15cd) as deficiency replacements.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Siemens HMS-2S addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed.

Modules[edit | edit source]

There are Siemens HTRI-D addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs[edit | edit source]

There are Siemens EL-300C end of line resistor plates on all sprinkler and signal circuits.