Lakewood Elementary

From FireAlarmPedia
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Main Electrical Room
System Type: Single-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous (Main Building)
Temporal (Portables)
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2017
Year Opened: 1994

Lakewood Elementary is an elementary school located at 2363 Setchfield Ave, Victoria, BC. It opened in 1994, was expanded in 2013, and had additional portables installed in 2017. The fire alarm system is mostly original.

System Specifications (1994-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS2-640C hybrid-addressable fire alarm system. The panel is located in the main electrical room. The main building and one portable are wired as conventional, while the other portables are addressable. The system runs Notifier’s FlashScan addressable protocol, and the system coding is continuous for all bells, and temporal for the horn/strobes.
The NFS2-640C replaced the original EST 6632 in 2017 due to not having enough capacity for the new portables.

Notification Appliances[edit | edit source]

Main Building[edit | edit source]

All notification appliances in the original school are Edwards 439D-10AWC vibrating bells (10” gong).
The 2013 addition has Mircom BL-10B motor bells (10” gong), also installed in each classroom.
There is also one Edwards MB10-24 motor bell (10” gong) in a classroom in the 2013 expansion.

Portables[edit | edit source]

Most portables have System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to electromechanical/15cd).
Some portables have Notifier KMS-10-24A motor bells (10” gong).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations in the original part are Edwards 270-SPOE conventional single-action pull stations.
The 2013 additions have Mircom MS-401 conventional single-action pull stations.
Most portables have Notifier NBG-12LX addressable dual-action pull stations.
The portable wired as conventional has a Notifier NBG-12L conventional dual-action pull station.

Automatic Detection Devices[edit | edit source]

There are Edwards 6250C conventional ionization smoke detectors in the original building.
The 2013 addition has Mircom “i3” 2W-BA conventional photoelectric smoke detectors.
Most portables have Notifier FSP-851A photoelectric smoke detectors, mounted on System Sensor B210LPA bases.
The portable wired as conventional has a System Sensor 5601A conventional 135 degree fixed-temperature/rate-of-rise heat detector.