FACP: Notifier NFS-640C FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2007 |
Morris Lofts is a condo complex located at 10154 103 St NW, in Edmonton, Alberta, Canada. The building was built in 2007, and the fire alarm system is original.
System Specifications[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier NFS-640C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All known notification appliances are System Sensor “SpectrAlert” P2415A horn/strobes (red, wall-mount, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices[edit | edit source]
There are likely Notifier FSP-851A addressable photoelectric smoke detectors throughout the common areas, mounted on Notifier B710LPA low-profile bases.
EOLs[edit | edit source]
There are Notifier EOL-CR end of line resistor plates on all signal circuits.