Honda Center

From FireAlarmPedia
System Specifications
FACP: Edwards EST3
FACP Location: Unknown
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: Slow Whoop + Message
Strobes Synchronized: No
Date of last known Upgrade: 2000s
Year Opened: 1993

The Honda Center is an arena located at 2695 East Katella Avenue, in Anaheim, California, USA. The arena has a seating capacity of 18,336, and is the home of the Anaheim Ducks of the National Hockey League. The arena opened in 1993, and the fire alarm system was upgraded in the 2000s.

System Specifications (2000s-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The evacuation signal is slow whoop, followed by the default voice message.

Notification Appliances[edit | edit source]

All notification appliances are Wheelock E70-24MCC-FW speaker/strobes (white, ceiling-mount, 70V, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-278 addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on EST SIGA-SB bases. The building is also equipped with a sprinkler system.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. [[]