More actions
System Specifications |
---|
FACP: Gamewell-FCI 7100 FACP Location: Unknown System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, Gentex Date of last known Upgrade: N/A Year Opened: 2010 |
Hampton Inn & Suites is a hotel chain owned by Hilton. The chain is headquartered in Mclean, Virginia, USA, and has locations globally. This particular hotel is located at 10 Hampton Ln, Wilder, Kentucky. The hotel opened in 2010, and the fire alarm system is original.
System Specifications[edit | edit source]
FACP[edit | edit source]
The building is protected by a Gamewell-FCI 7100 addressable fire alarm system. The panel location is unknown. The system runs Gamewell-FCI’s Velociti addressable protocol, and the system coding is temporal.
Annunciators[edit | edit source]
There is a Gamewell-FCI LCD-7100 annunciator behind the front desk.
Notification Appliances[edit | edit source]
Most notification appliances are Gentex “Commander 3” Gentex GEC3-24WR horn/strobes (red, wall-mount, set to 15cd/electromechanical).
There are Gentex GX93-R mini-horns (red, wall-mount) in each guest room.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Gamewell-FCI MS-7AF addressable dual-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Gamewell-FCI ASD-PL2F addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B710LP bases.
Modules[edit | edit source]
There are Gamewell-FCI AMM-4F addressable monitor modules supervising the sprinkler system’s tamper and flow switches.