River Cree Twin Rinks

From FireAlarmPedia
System Specifications
FACP: Notifier NFS2-3030C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2014
Year Opened: 2006

River Cree Twin Rinks is a twin arena complex located in the River Cree Resort & Casino, at 300 East Lapotac Blvd, Enoch, Alberta. It houses two NHL-sized rinks. The building was built in 2006, and the fire alarm system is mostly original.

System Specifications (2006-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

Most notification appliances are System Sensor “SpectrAlert” P2415A horn/strobes (red, wall-mount, 15cd).
There are some System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd) as deficiency replacements.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851A addressable photoelectric smoke detectors in some areas, mounted on Notifier B710LPA bases.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on each SLC.

EOLs[edit | edit source]

There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.