Shepard Landfill Building D

From FireAlarmPedia
System Specifications
FACP: EST iO500
FACP Location: Main Mechanical Room
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR (Panel NACs)
24VDC (Booster NACs)
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2013

Shepard Landfill is a waste management facility owned and operated by the City of Calgary. The facility is located at 12111 68 Street SE, in Calgary, Alberta, Canada. This page will cover Building D, which is a vehicle storage garage. The building was built in 2013, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main mechanical room. The system runs EST’s Signature addressable protocol, and the system coding is temporal.

Boosters[edit | edit source]

There are eight EST BPS10A booster power supplies; 4 of which are located in the main mechanical room, and 4 are located in the main electrical room.

Notification Appliances[edit | edit source]

Vehicle Bays[edit | edit source]

All audible notification appliances are Edwards “AdaptaHorn” 889D-AW explosion-proof remote horns (red, wall-mount).
All visual notification appliances are Edwards 116DEGEX-FJ explosion-proof remote strobes (125cd)

Mechanical Rooms[edit | edit source]

All notification appliances are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).

Wash Bay[edit | edit source]

All notification appliances are Edwards “Integrity” 757-7A-T horn/strobes (red, wall-mount, 15/75cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations in the vehicle bays are Edwards MPSR1-S45W conventional explosion-proof single-action pull stations. These are wired to EST SIGA-CT1 addressable monitor modules.
All other areas have EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in all mechanical rooms, mounted on EST SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are also EST SIGA-IM addressable isolator modules on each SLC loop.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.