FACP: Mircom FX-2000 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 2010 |
The Calgary Fire Department is the fire department serving The City of Calgary. This page will cover Station 6, located at 360 8 Street SW, in Calgary, Alberta, Canada. The station was built in 2010, and the fire alarm system is original.
System Specifications[edit | edit source]
FACP[edit | edit source]
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Mircom’s CLIP addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All notification appliances are Mircom “Select-A-Horn/Strobe” FHS-240R horn/strobes (red, wall-mount, set to broadband/15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations but one are Mircom MS-401AD addressable single-action pull stations.
There is an Edwards 270-SPO conventional single-action pull station wired to a Mircom MIX-M501MA addressable monitor module at the main entrance as a deficiency replacement.
Automatic Detection Devices[edit | edit source]
There are Mircom MIX-2251BA addressable photoelectric smoke detectors throughout the second floor corridors, mounted on System Sensor B710LPA bases.
There are System Sensor DNRA duct smoke detector housings with Mircom MIX-2251BA addressable photoelectric heads on all make up air units.
Modules[edit | edit source]
There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There is a Mircom MIX-M500DMA addressable dual-input monitor module supervising the generator’s run and trouble contacts. <br.There are Mircom MIX-M500RA addressable relay modules for MUA and central vacuum shutdown.
There are System Sensor M500XA isolator modules on the SLC.
EOLs[edit | edit source]
There are Mircom MP-300 end of line resistor plates on all sprinkler, generator and signal circuits.