RONA (Sunridge)

From FireAlarmPedia
System Specifications
FACP: Kidde VS4
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2024
Year Opened: 1998

RONA is a Canadian hardware store chain. This particular store is located at 2665 32 St NE, Calgary, Alberta. The store opened in 1998, and the fire alarm system was upgraded in 2024.

System Specifications (2024-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Kidde VS4 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Kidde’s GSA addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All notification appliances are Kidde “Genesis” G4AVRN horn/strobes (red, wall-mount, no marking, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Kidde GSA-M270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed. The building has a sprinkler system.

Modules[edit | edit source]

There are Kidde GSA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Kidde GSA-CR addressable relay modules serving various purposes.
There are Kidde GSA-IM isolator modules on the SLC’s.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.

Former System Specifications (1998-2024)[edit | edit source]

Former System Specifications
FACP: Edwards EST2
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 2010s?
Year Installed: 1998
Year Decommissioned: 2024

FACP[edit | edit source]

The building was protected by an Edwards EST2 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Edwards’ Signature addressable protocol, and the system coding was continuous.

Notification Appliances[edit | edit source]

Most notification appliances were General Signal MB10-24 motor bells (10” gong) mounted on Edwards 403-5A-R strobe plates (15cd).
There was one Edwards MB10-24 motor bell (10” gong) on the existing strobe plate as a deficiency replacement.
One bell was on a Wheelock RSSP-24MCW strobe plate (red, set to 15cd) as a deficiency replacement.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were EST SIGA-270 addressable single-action pull stations.


Automatic Detection Devices[edit | edit source]

None noticed. The building has a sprinkler system.

Modules[edit | edit source]

There were EST SIGA-WTM addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There were EST SIGA-CR addressable relay modules serving various purposes.

EOLs[edit | edit source]

There were Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.

Permits[edit | edit source]

Permit issued May 6, 2024.  Project scope was Fire Alarm Repair/Upgrade. Source: Calgary MyProperty