System Specifications
FACP: Edwards iO1000
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR (FACP)
24VDC (Boosters)
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2019

ATS Healthcare is a healthcare supply distribution company. This page will cover the Calgary branch, located at 5480 61 Ave SE, in Calgary, Alberta, Canada. The building was built in 2019, and the fire alarm system is original.

System Specifications

FACP

The building is protected by an Edwards iO1000 addressable fire alarm system. The panel is located in the main electrical room. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.

Booster Panels

There are three Edwards BPS10AC 10 amp booster power supplies on the system: two in the main electrical room, and one in the ATS data room.

Notification Appliances

Most notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Some areas have Edwards GC-HDVM horn/strobes (white, ceiling-mount, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red, 15/75cd) outside the main electrical room.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are Edwards SIGA-PD addressable photoelectric smoke detectors in all data, janitor, sprinkler and electrical rooms, mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the fire pump, generator, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on the SLC.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.