| System Specifications |
|---|
| FACP: EST QuickStart QS4 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (FACP) 24VDC (Boosters) System Coding: Temporal Strobes Synchronized: Yes, Self-Sync Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2009 |
Acclaim Hotel by Clique Calgary Airport is a mid-range hotel located at 123 Freeport Blvd NE, in Calgary, Alberta, Canada. The building was built in 2009, and the fire alarm system is original excluding deficiency replacements.
System Specifications
FACP
The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is temporal.
Annunciators
There is an EST RLCD annunciator behind the front desk.
Booster Panels
There are Edwards BPS6AC 6-amp booster power supplies in each electrical room.
Notification Appliances
All common area notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
All guest rooms have Edwards 683-1C silenceable mini-horns (white) paired with Edwards G1-VM remote strobes (white, wall-mount, no marking, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout all corridors, at the top of each stairwell, and in each elevator shaft.
There are EST SIGA2-PS and Edwards SIGA-PD/OSD addressable photoelectric smoke detectors as deficiency replacements.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in all mechanical and laundry rooms on floors 1-4.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on all air handling units.
There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors in the basement laundry and mechanical rooms.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the heat detector zones, the kitchen suppression systems, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on both SLCs.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all Class B signal circuits.