| System Specifications |
|---|
| FACP:EST iO500 FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2015 Most Recent Known Modification: N/A Year Opened: 1914, 1974 |
CPKC is a North American railway company headquartered in Calgary, Alberta. This page will cover Building 3 (Pavilion) of the Ogden Campus, located at 7550 Ogden Dale Road SE, in Calgary, Alberta, Canada. The building was built in 1914, was halved in 1974, and was renovated in 2015. The fire alarm system was upgraded as part of the 2015 renovation.
System Specifications (2015-present)
FACP
The building is protected by an EST iO500 addressable fire alarm system. The panel is located at the main entrance. The system runs EST's Signature addressable protocol, and the system coding is temporal.
Notification Appliances
All indoor notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red, 15/75cd) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA2-PS addressable photoelectric smoke detectors at the top of each stairwell, in all storage rooms, in most closets, and in all electrical rooms.
There are EST SIGA2-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the janitor room, the kitchen, and in one closet.
All detectors are mounted on EST SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the kitchen suppression system, the NOVEC suppression system, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on the SLC.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all suppression, sprinkler and signal circuits.