| System Specifications |
|---|
| FACP: Mircom FX-2000 FACP Location: Rear Exit System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2020 |
Castlebrook Greens is an apartment complex owned and operated by Broadstreet. This page will cover Building A, located at 17430 110 St NW, in Edmonton, Alberta, Canada. The building was built in 2020, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located at the rear exit. The system runs Mircom's Advanced addressable protocol, and the system coding is temporal.
Booster Panels
There are Mircom INX-10A addressable 10-amp booster power supplies on some floors.
Notification Appliances
All common area notification appliances are System Sensor "L-Series" P2RLA-E horn/strobes (red, wall-mount, english lettering, set to 15cd).
All suite bedrooms have System Sensor MHWZA silenceable mini-horns (white); all suite living rooms have System Sensor SWLA remote strobes (white, wall-mount, bilingual lettering, set to 15cd).
Initiating Devices
PulL Stations
All pull stations are Mircom MS-401AP addressable single-action pull stations.
Automatic Detection Devices
There are Mircom MIX-2251APA addressable photoelectric smoke detectors throughout all corridors, and at the top of each stairwell.
There are Mircom MIX-5251HAPA addressable 190°F fixed-temperature heat detectors in the boiler room.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the janitor room.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There is a System Sensor "Innovair Flex" DNRA duct smoke detector housing equipped with a Mircom MIX-2251APA addressable photoelectric head on the air handling unit.
Modules
There are Mircom MIX-M501MAPA addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RAPA addressable relay modules serving various purposes.
There are System Sensor M500XA isolator modules on the SLC.
EOLs
There are Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.