Centre 70

From FireAlarmPedia
System Specifications
FACP: Simplex 4100ES
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 2010s
Year Opened: 1977

Centre 70 is an office/medical building located at 7015 Macleod Tr SW, Calgary, AB. The building houses multiple tenants on the main floor. The building was completed in 1977, and the fire alarm system was mostly upgraded in the 2010s, with parts in age from 1977 to present.

System Specifications

FACP

The building is protected by a Simplex 4100ES conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is continuous.

Notification Appliances

Most notification appliances are Simplex 2901-9724 motor bells (10" gong).
The following notification appliances are present on the system as deficiency replacements, from most common to least.

  • Wheelock MB-G6-24 motor bells (6" gong)
  • Simplex 2901-9723 motor bells (6" gong)
  • System Sensor SSM24-6A motor bells (6" gong)
  • Mircom BL-6B motor bells (6" gong)
  • Potter MBA-6-24 motor bells (6" gong) on Wheelock RSSP-24MCW strobe plates (red, set to 15cd) in two units
  • Simplex 2901-9723 motor bells (6" gong) on Wheelock RSSP-24MCW strobe plates (red, set to 15cd) in the same units
  • Edwards 439D-6AWC vibrating bells (6" gong)
  • Edwards 439D-10AWC vibrating bell (10" gong)
  • Notifier KMS-6-24A motor bell (6" gong)
  • Notifier KMS-10-24A motor bell (10" gong)

Initiating Devices

Pull Stations

Most pull stations are the original Simplex 4251-20 conventional single-action pull stations.
The following pull stations are present on the system, listed from most common to least as deficiency replacements.

  • Simplex MS-301C conventional single-action pull stations
  • Edwards 275-C111 conventional single-action pull stations
  • Edwards 270-SPO conventional single-action pull station in the upper parking garage
  • Mircom conventional single-action pull station
  • Simplex 2099-9754 conventional single-action pull station

Automatic Detection Devices

There are FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors in most tenants.
There are also Potter CR-135W conventional 135°F fixed-temperature/rate-of-rise heat detectors in the mix.
There are also Mirtone 73330 conventional 135°F fixed-temperature heat detectors.
The stairwells, 8th floor copier room and some tenant rooms have System Sensor "i3" C2W-BA conventional photoelectric smoke detectors; the 8th floor copier room one replaced a Mircom MIR-1400A conventional ionization smoke detector in 2025.
The 9th floor copy room has a Simplex 2098-9560 conventional ionization smoke detector.
The main air handling unit has a Simplex 4098-9688 conventional duct smoke detector housing with a Simplex 4098-9601 photoelectric head.