Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

FedEx Calgary Supply Chain

From FireAlarmPedia
System Specifications
FACP: Edwards EST3
FACP Location: Main Electrical Room
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, Self-Sync
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2001

FedEx Calgary Supply Chain is a Canadian Tire distribution centre located at 6336 114 Ave SE, in Calgary, Alberta, Canada. The building was built in 2001, and the fire alarm system is original.

System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. This is a networked system; the main node is located in the main electrical room. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, and the alarm signal coding is temporal.

Annunciators

There are Edwards EST3-LCDANN annunciators at the security desk and gatehouse.

Booster Panels

There are over 20 Edwards BPS6AC 6 amp booster power supplies on the system.

Notification Appliances

Most notification appliances are General Signal MB10-24 motor bells (10" gong) mounted on Edwards 403-5A-R strobe plates (15cd).
Areas with higher ambient noise levels have Edwards 5520D-AW horns paired with high-output red strobes.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are EST SIGA2-PS addressable photoelectric smoke detectors on all pick mods.
There are EST SIGA-PS addressable photoelectric smoke detectors in some areas.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in all electrical rooms.
All detectors are mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising various auxiliary functions, such as the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.