Holy Spirit School (Cochrane)

From FireAlarmPedia
System Specifications
FACP: Notifier NFS-320C
FACP Location: Mechanical Room?
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: N/A
Year Opened: 2022

Holy Spirit School is an elementary school located at 200 Fireside Drive, in Cochrane, Alberta, Canada. The school is owned by the Calgary Catholic Separate School District, and opened in 2022 to replace the old building after the lease expired. The fire alarm system is original.

System Specifications (2022-present)

FACP

The school is protected by a Notifier NFS-320C addressable fire alarm system. The panel is likely located in a mechanical room. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Annunciators

There is a Notifier LCD2-80 annunciator and a Notifier ACM-24AT LED annunciator at the main entrance.

Notification Appliances

All of the notification appliances except for one are from System Sensor's "L-Series" line of products.

Most notification appliances are System Sensor P2RLA horn/strobes (red, wall-mount, set to 15cd, bilingual). These are also in each classroom.

The main office and hallways with low ceilings have System Sensor PC2RLA horn/strobes (red, ceiling-mount, set to 30cd bilingual).

The main floor washrooms have System Sensor SCRLA remote strobes (red, ceiling-mount, bilingual, set to 30cd).

The second floor washrooms have System Sensor SRLA remote strobes (red, wall-mount, bilingual, set to 30cd).

For outdoor notification, there is a System Sensor “SpectrAlert Advance” P2RKA weatherproof horn/strobe (red, wall-mount) near the main entrance.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-951A addressable photoelectric smoke detectors throughout the school.

Some areas have Notifier FST-951RA addressable 135°F fixed-temperature/rate-of-rise heat detectors.

These are mounted on System Sensor B300A-6 bases in most areas, and on B224BIA isolator bases in the stairwells.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Notifier FRM-1A addressable relay modules serving various purposes.

There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end-of-line resistors on all sprinkler and signal circuits.