| FACP: Notifier NFS2-640C FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: 2010s, 2 Pulls Year Opened: 2008 |
KBL Projects is an environmental health service located at 10501 Barlow Tr SE, Calgary, Alberta. This page will cover the north building. It was built in 2008, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
This panel is part of KBL's NOTI-FIRE-NET network, and is networked to the other two buildings on site.
Notification Appliances
All indoor notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there are System Sensor HRKA weatherproof remote horns (red) outside the rear of the building, and there is a System Sensor P2RKA weatherproof horn/strobe (red, wall-mount) outside the main entrance.
Initiating Devices
Pull Stations
Most pull stations are Notifier MPS-950B conventional single-action pull stations.
There are Mircom MS-401 conventional single-action pull stations as deficiency replacements, with one Edwards 270-SPO conventional single-action pull station in the shop area.
All pull stations are wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices
There are Notifier FSI-851A addressable ionization smoke detectors at the top of each stairwell.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in all electrical and mechanical rooms.
All detectors are mounted on Notifier B710LPA bases.
Modules
There are Notifier FMM-101A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.