| System Specifications |
|---|
| FACP: Notifier NFS2-640C FACP Location: Main Mechanical Room System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2008 |
KBL Projects is an environmental health service located at 10501 Barlow Tr SE, Calgary, Alberta. This page will cover the wash bay building. It was built in 2008, and the fire alarm system is original.
System Specifications (2008-present)
FACP
The building is protected by a Notifier NFS2-640C conventional fire alarm system. The panel is located in the main mechanical room. The panel has a Notifier XP10-MAA zone card to accommodate the system's conventional technology, and the system coding is temporal.
This panel is part of the facility's NOTI-FIRE-NET network.
Notification Appliances
All notification appliances are System Sensor "SpectrAlert Advance" P2RKA weatherproof horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier MPS-950B conventional single-action pull stations.
Automatic Detection Devices
There are FDD CF-135MP conventional moisture-proof 135°F fixed-temperature heat detectors throughout the wash bays.
There are FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors in all electrical and mechanical rooms.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all circuits.