Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Kananaskis Mountain Lodge

From FireAlarmPedia
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Room Behind Front Desk
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2018
Year Opened: 1987

The Kananaskis Mountain Lodge is a 3-story hotel located at 1 Centennial Drive, Kananaskis, AB. It was built in 1987 as Delta Lodge, and became Pomeroy Kananaskis Mountain Lodge in 2018. The fire alarm system was installed after the renovation.

NOTE: This page may not be accurate as there is conflicting information from sources. This page should not be used for official purposes.

System Specifications (2018-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in a room behind the front desk. The panel is fitted with a Notifier NCA-2 display. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All notification appliances are from System Sensor's "SpectrAlert Advance" line of products. All common area notification appliances are System Sensor P2RA horn/strobes (red, wall-mount, set to 15cd). The guest rooms contain System Sensor MHW mini horns (white).

There are Edwards 439D-10AWC vibrating bells (10" gong) left over in the weight room and pool area, however it is unknown how that portion works.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations. However, the Edwards 275-C111 conventional pull stations still exist in the pool area and weight room, and it is unknown if these are still in use.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851A addressable photoelectric smoke detectors on B210LPA bases throughout the hotel.

Modules[edit | edit source]

There are likely Notifier FMM-1A monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.

Former System Specifications (1987-2018)[edit | edit source]

System Specifications
FACP: Edwards 6500

FACP Location: Room Behind Front Desk
System Type: Conventional (Two-Stage)
System Line Voltage: 120VAC
NAC Voltage: 24VDC

System Coding: 20BPM (first stage)

Continuous (GA)
Date of last known Upgrade: 2000s
Year Decomissioned: 2018

FACP[edit | edit source]

The building was protected by an Edwards 6500 conventional fire alarm system. The panel was located in a room behind the front desk. The system was configured for two-stage operation. First stage coding was 20BPM, followed by continuous in general alarm.

Notification Appliances[edit | edit source]

All notification appliances except for one were the original Edwards 439D-10AWC vibrating bells (10" gong). They were mounted behind grills in all common areas except for the parkade, pool area, basement and The Fireweed Grill. There was a Notifier KMS-6-24A motor bell (6" gong) on the third floor as a deficiency replacement.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were Edwards 275-C111 conventional pull stations. Despite being two-stage, two devices had to be activated to go into general alarm.

Automatic Detection Devices[edit | edit source]

The smoke detectors were a mix of System Sensor 1412A ionization smoke detectors and Edwards 6264B ionization smoke detectors.