Northgate Centre

From FireAlarmPedia
System Specifications
FACP: Edwards EST3
FACP Location: CACF Room
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (alarm)
Strobes Synchronized: Yes, EST
Date of last known Upgrade: 2002
Most Recent Known Modification: N/A
Year Opened: 1965, 1977, 1986

Northgate Centre is a shopping mall located at 9499 137 Ave NW, Edmonton, Alberta. The mall contains over 70 stores, and is anchored by Safeway and Walmart. The mall opened in 1965, and was expanded in 1977 and 1986. A major renovation took place in 2002, and the fire alarm system was upgraded then.

System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the CACF room. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal for the alarm signal.

Annunciators

There is an Edwards EST3-LCDANN annunciator at Entrance B.

Booster Panels

There are multiple Edwards BPS6A 6-amp booster power supplies on the system.

Notification Appliances

All notification appliances are Edwards "Integrity" 757-5A-T horn/strobes (red, wall and ceiling-mount, 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage pull stations.

Automatic Detection Devices

There are EST SIGA-IS addressable ionization smoke detectors in some rooms, mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-WTM addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.

EOLs

There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.