More actions
| System Specifications |
|---|
| FACP: Edwards EST3 FACP Location: CACF Room System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) Temporal (alarm) Strobes Synchronized: Yes, EST Date of last known Upgrade: 2002 Most Recent Known Modification: N/A Year Opened: 1965, 1977, 1986 |
Northgate Centre is a shopping mall located at 9499 137 Ave NW, Edmonton, Alberta. The mall contains over 70 stores, and is anchored by Safeway and Walmart. The mall opened in 1965, and was expanded in 1977 and 1986. A major renovation took place in 2002, and the fire alarm system was upgraded then.
System Specifications
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the CACF room. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal for the alarm signal.
Annunciators
There is an Edwards EST3-LCDANN annunciator at Entrance B.
Booster Panels
There are multiple Edwards BPS6A 6-amp booster power supplies on the system.
Notification Appliances
All notification appliances are Edwards "Integrity" 757-5A-T horn/strobes (red, wall and ceiling-mount, 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage pull stations.
Automatic Detection Devices
There are EST SIGA-IS addressable ionization smoke detectors in some rooms, mounted on EST SIGA-SB bases.
Modules
There are EST SIGA-WTM addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
EOLs