System Specifications
FACP: None
System Type: 120V Hardwired
System Line Voltage: 120VAC
System Coding: Continuous
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 1973

Parkview Condos is a condo building located at #23, 1703 11 Ave SW, in Calgary, Alberta, Canada. The building was built in 1973, and the fire alarm system is original.

System Specifications

Please note that this information is accurate to 2022. The building is protected by a 120V hardwired fire alarm system, with bells and initiating devices wired in series-parallel. The system coding is continuous.

Notification Appliances

All notification appliances are Edwards "Durabel" 6000D vibrating bells (6" gong).

Initiating Devices

Pull Stations

All pull stations are Edwards 270-SPO conventional single-action pull stations.

Automatic Detection Devices

There are American Sensors ESA5011 ionization smoke alarms in all corridors and at the top of each stairwell.
There are a mix of FDD CR-135 and System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors in the storage and laundry rooms.
There are FDD CF-200 conventional 200°F fixed-temperature heat detectors in the electrical and furnace rooms.