Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Mail is now working! Feel free to request an account. Accounts are available to invested enthusiasts/technicians in the industry. :)

Royal Alexandra Hospital - Robbins Pavilion & Women's Health Centre

From FireAlarmPedia
System Specifications
FACP: Siemens FireFinder XLS
FACP Location: Unknown
System Type: Two-Stage Networked Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: Unknown
Strobes Synchronized: Yes, Siemens
Date of last known Upgrade: N/A
Year Opened: 2008

The Royal Alexandra Hospital is a hospital in Edmonton, Alberta, Canada. This page will cover the Robbins Pavilion & Women’s Health Centre, located at 10240 Kingsway Ave NW. The building was built in 2008, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Siemens FireFinder XLS addressable fire alarm system. This system is part of a hospital-wide network. The system runs Siemens’ FirePrint addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation; the messages and/or tones are unknown at this time.

Annunciators

There are Siemens SSD annunciators at each nurse’s station.

Notification Appliances

The notification appliances are a mix of Siemens CR-8100-70 remote speakers and speaker/strobes (specific model unknown).

Initiating Devices

Pull Stations

All pull stations are Siemens HMS-2S addressable two-stage single-action pull stations.

Automatic Detection Devices

There are Siemens HFP-11 addressable multisensor smoke/heat detectors throughout all areas, mounted on Siemens DB-11 bases.

Modules

There are Siemens HTRI-D addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Siemens HTRI-R addressable relay modules serving various purposes.

EOLs

There are Siemens EL-300C end of line resistor plates on all sprinkler and signal circuits.