FACP: Notifier NFS2-640C FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2014 Year Opened: 2000 |
The Royal Canadian Lodge is a 4-star hotel located at 459 Banff Ave, in Banff, Alberta, Canada. The hotel was built in 2000, and the fire alarm system was upgraded in 2014.
System Specifications (2014-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All notification appliances are System Sensor “SpectrAlert Advance” P2WA horn/strobes (white, wall-mount, set to 15cd), installed in all common areas and guest rooms.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout most common areas.
Some areas have Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on System Sensor B210LPA bases.
Modules[edit | edit source]
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.