Scarborough Town Centre

From FireAlarmPedia
System Specifications
FACP: Edwards EST3
FACP Location: Security Office
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (alert)
Temporal (Alarm)
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 1999
Most Recent Known Modification: 2010s (strobes)
Year Opened: 1972

Scarborough Town Centre is a shopping mall located at 300 Borough Dr, Scarborough, Ontario, Canada. The mall is managed by Oxford Properties. The mall opened in 1973, and was extensively renovated from 1998-1999. The fire alarm system was upgraded in 1999.

System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the security office. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal for the alarm signal.

Booster Panels

There are multiple Edwards BPS6A 6-amp booster power supplies throughout the building.

Notification Appliances

Most notification appliances are General Signal MB10-24 motor bells (10" gong).
Some areas have Edwards MB6-24 motor bells (6" gong).
There are some Edwards MB10-24 motor bells (10" gong) as deficiency replacements.
Most bells are mounted behind grilles.
There are Edwards "Genesis" G1R-VM remote strobes (red, wall-mount, no marking, set to 15cd) in some areas.

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors in some areas, mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches, kitchen suppression systems, generator run and trouble, plus the fire pump's contacts.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM isolator modules on the SLC.
There are EST SIGA-CC1 addressable control modules for triggering the boosters.

EOLs