Scenic Bow Group Home 23

From FireAlarmPedia
System Specifications
FACP: Simplex 4007ES
FACP Location: Main Staff Office
System Type: Two-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: N/A
Date of last known Upgrade: 2023
Year Opened: 1987

Scenic Bow Place is a group home complex owned by Alberta Health Services. This page will cover Group Home 23, located at #130 100 Scenic Bow Place NW, in Calgary, Alberta, Canada. The home was built in 1987, and the fire alarm system was fully replaced in 2023.

System Specifications (2023-present)

FACP

The building is protected by a Simplex 4007ES hybrid-addressable fire alarm system. The panel is located in the main staff office. The system runs Simplex’s IDNet addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal. The general alarm timer length is 5 minutes.

Notification Appliances

All notification appliances are Simplex “TrueAlert” 49CMT-WRF remote horns (red, wall-mount, set to horn).

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations.

Automatic Detection Devices

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in most areas.
There are Simplex 4098-9734 addressable 190°F fixed-temperature/rate-of-rise heat detectors in the kitchen, laundry room, and washrooms.
All aforementioned detectors are mounted on Simplex 4098-9792 bases.
There are Simplex 4098-9601 conventional photoelectric smoke detectors in the main living area and at the top of the basement stairwell.
There are Simplex 4098-9755 addressable duct smoke detectors with Simplex 4098-9714 photoelectric heads on all fan units.
There are Simplex 4098-XAD-110 addressable photoelectric aspirating smoke detectors supervising the client room and padded room.

Modules

There are Simplex 4090-9001 addressable monitor modules monitoring damper statuses.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on the SLC.

EOLs

There are Simplex 2081-9040C end of line resistor plates on all conventional and signal circuits.