Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Servus Arena - Red Deer

From FireAlarmPedia
System Specifications
FACP: Edwards EST3X
FACP Location: Main Entrance Vestibule
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2018

Servus Arena is an arena located at 4725 43 Street, in Red Deer, Alberta, Canada. The arena is owned and operated by The City of Red Deer. The arena was built in 2018, and replaced the original Red Deer Arena. The fire alarm system is original.

System Specifications

FACP

The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Edwards' Signature addressable protocol, is equipped with voice evacuation, and is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is a temporal tone. Live announcements are made over the system in lieu of pre-recorded messages.

Notification Appliances

Most notification appliances are Edwards "Genesis" G4R-S7VM speaker/strobes (red, wall-mount, no marking, 70V, set to 15cd).
Some areas have Edwards GCF-S7VM speaker/strobes (white, ceiling-mount, FIRE marking, 70V, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are Edwards SIGA-PD addressable photoelectric smoke detectors in all elevator lobbies and at the top of each stairwell.
There are Edwards SIGA-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors in the mechanical room.
All detectors are mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the kitchen suppression system, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all kitchen suppression, sprinkler and signal circuits.