| System Specifications |
|---|
| FACP: Edwards iO1000 FACP Location: Shop SW Exit System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (FACP) 24VDC (Booster) System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Most Recent Known Modification: 2025, Mezz Smokes Year Opened: 2008 |
Standard General is a paving contracting company. This page will cover the Calgary shop, located at 9660 Enterprise Way SE, in Calgary, Alberta, Canada. The building was built in 2008, and the fire alarm system is original.
System Specifications
FACP
The building is protected by an Edwards iO1000 addressable fire alarm system. The panel is located at the southwest shop exit. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.
Booster Panels
There is an Edwards BPS6AC 6-amp booster power supply next to the main FACP.
Notification Appliances
Most notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
The wash bay has Edwards "Integrity" 757-7A-T horn/strobes (red, wall-mount, 15/75cd, enhanced) due to the wet nature of the area.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors at the top of each stairwell.
There are Edwards SIGA-OSD addressable optical smoke detectors on the mezzanine.
All detectors are mounted on EST SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.