| System Specifications |
|---|
| FACP: Edwards EST3 FACP Location: Main Electrical Room System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) 120BPM (Alarm) Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2015 Most Recent Known Modification: N/A Year Opened: 1984, 1988 |
Strathmore District Health Services is a hospital located at 200 Brent Blvd, in Strathmore, Alberta, Canada. The hospital is owned and operated by Alberta Health Services. The building was built in 1984, was expanded in 1988, and the fire alarm system was upgraded in 2015.
System Specifications (2015-present)
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the main electrical room. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert signal is 20BPM, and the alarm signal is 120BPM.
Annunciators
There are Edwards EST3-LCDANN annunciators at the nurse's station, in one room, and in the main entrance vestibule.
Notification Appliances
All notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout most areas, and at the top of each stairwell.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in areas such as mechanical rooms and elevator shafts.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on all air handling units, with EST SIGA-LED remote indicators connected to each detector.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the kitchen suppression system, the generator's run/trouble contacts, the fire pump's run/trouble contacts, the pre-action system's run/trouble contacts, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.
There are EST SIGA-MCC1S addressable control modules serving as NACs.
There are EST "Genesis SignalMaster" G1M-RM modules for 4-wire horn/strobe operation.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.
Former System Specifications (1984-2015)
| Former System Specifications |
|---|
| FACP: Simplex 2001 FACP Location: Main Electrical Room System Type: Two-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) 90BPM (Alarm) Strobes Synchronized: N/A Most Recent Known Modification: N/A Year Installed: 1984 Year + Reason Decommissioned: 2015, Lifecycle Upgrade |
FACP
The building was protected by a Simplex 2001 conventional fire alarm system. The panel was located in the main electrical room. The system was configured for two-stage operation. The alert signal was 20BPM, and the alarm signal was 90BPM.
Annunciators
There were Simplex annunciators in some areas.
Notification Appliances
All notification appliances were Simplex 4080-C5 vibrating bells (6" gong).
Initiating Devices
Pull Stations
All pull stations were Simplex 2099-9905 conventional two-stage single-action pull stations.
Automatic Detection Devices
There were Simplex 2098-9544 conventional ionization smoke detectors throughout the building.
There were Simplex 4255-51 conventional 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
EOLs
There were Simplex 2081-9018C end of line resistor plates on all circuits.