Travelodge by Wyndham Edmonton West

From FireAlarmPedia
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: N/A
Date of last known Upgrade: 2019
Most Recent Known Modification: 2022, Pulls
Year Opened: 1980

Travelodge is a chain of budget hotels owned by Wyndham. This particular hotel is located at 18320 Stony Plain Road, in Edmonton, Alberta, Canada. The building was built in 1980, and the fire alarm system is partially original.

System Specifications

FACP

The building is protected by a Notifier NFS2-640C hybrid-addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and utilizes Notifier XP6-MAA zone cards for conventional devices. The system coding is continuous.
This system is NOT Two-Stage.

Notification Appliances

Most notification appliances are Edwards MB10-24 motor bells (10" gong).
There are Edwards MB6-24 motor bells (6" gong) in the laundry room.
There are Potter MBA-10-24 motor bells (10" gong) in the restaurant.
There is an Edwards 439D-10AWC vibrating bell (10" gong) in the basement.

Initiating Devices

Pull Stations

Most pull stations are Edwards 270-GAO conventional two-stage single-action pull stations.
The 5th, 4th and main floors have Mirtone 73304 conventional two-stage single-action pull stations.
The restaurant, kitchen and east main floor stair exit have Notifier MPS-950B conventional single-action pull stations as deficiency replacements.
There are Edwards 270-GAOB conventional two-stage single-action pull stations with bilingual lettering on the 2nd floor of the east tower.
There are Chubb 950-1004 conventional two-stage single-action pull stations in the basement, with one present in Smitty's.

Automatic Detection Devices

There are System Sensor C2W-BA conventional photoelectric smoke detectors throughout all hotel corridors, and in the lobby storage room.
There are FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors in most storage, housekeeping, staff, maintenance, locker and laundry rooms.
There are FDD CF-135 conventional 135°F fixed-temperature heat detectors in the mechanical room, phone rooms, the pool storage room, the generator room, and some storage and housekeeping rooms.
There are FDD CF-200 conventional 200°F fixed-temperature heat detectors in the boiler room.
There are Edwards 281B-PL conventional 135°F fixed-temperature/rate-of-rise heat detectors in some housekeeping rooms, and at the generator entrance.
There are Edwards 281C conventional 135°F fixed-temperature/rate-of-rise heat detectors in some storage rooms.
There is a Mirtone 73330 conventional 135°F fixed-temperature heat detector in the laundry room closet.
There are Notifier FSP-851A addressable photoelectric smoke detectors at each elevator lobby, at the top of each stairwell, and in all elevator machine rooms.
There is a Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detector in the arcade storage room.
All addressable detectors are mounted on System Sensor B210LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the fire pump flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all conventional, signal, and sprinkler circuits (excluding two sprinkler circuits).
One sprinkler circuit has a Notifier EOL-CR end of line resistor plate, while another has a Notifier EOL-CW end of line resistor plate.