Westlink Park

From FireAlarmPedia
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestiuble
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2014

Westlink Park is an office building located at 16826 107 Ave NW, Edmonton, Alberta. The building was completed in 2014, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All indoor notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
For exterior notification, there is a System Sensor P2RKA weatherproof horn/strobe (red, wall-mount, set to 75cd) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable single-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building.
Some rooms have Notifier FST-851A addressable 135°F fixed-temperature heat detectors.
All detectors are mounted on System Sensor B210LPA bases.

Modules

There are Notifier FDM-1A addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.