System Specifications |
---|
FACP: Notifier NFS2-3030C FACP Location: CACF Room System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 70VRMS (audible) 24VDC (visual) System Coding: 20BPM chime + message (Alert) Temporal Tone + message (Alarm) Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2019 Year Opened: 1980 |
10250 101 Street NW is the address given to an office tower in Edmonton, Alberta. The building was completed in 1980, and underwent a major renovation and revitalization in 2019. The fire alarm system was installed during the renovation.
System Specifications (2019-present)
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the CACF room. The system runs Notifier's FlashScan addressable protocol, and is equipped with Notifier’s "Digital Voice Command (DVC)" voice evacuation system. The system is configured for two-stage operation. The alert signal is a 20BPM chime, followed by a temporal tone for the alarm signal. Both signals play the default Notifier messages.
Annunciators
There is a Notifier LCD-160 annunciator in the east entrance vestibule.
Booster Panels
There are Notifier FCPS-24S8C 8-amp booster power supplies on each floor, powering the strobes. There are numerous Notifier DAA2-5070 50-watt amplifiers powering the speakers.
FACP Accessories
There is a Notifier ONYXWorks workstation computer on the system.
Notification Appliances
Most notification appliances are System Sensor "L-Series" SPSCWLA speaker/strobes (white, ceiling-mount, set to 15cd/70V).
There are System Sensor SPCWLA speakers (white, ceiling-mount) for additional audible coverage.
Each washroom has a System Sensor SCWLA remote strobe (white, ceiling-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier N-MPS-2A addressable two-stage pull stations.
Automatic Detection Devices
There are Notifier FSP-951A addressable photoelectric smoke detectors throughout, mounted on System Sensor B300A-6 bases.
The elevator lobbies have Notifier FSP-851A addressable photoelectric smoke detectors, mounted on System Sensor B210LPA bases.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier FTM-1A addressable fire phone modules supervising all fire phones.
There are Notifier ISO-XA isolator modules on the SLCs.
Firefighter's Telephones
There are Notifier FT-300N firefighter's telephones on each floor.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.
Sequence of Operation
This system is configured for floor-by-floor two-stage operation. A first stage alarm initiated on any floor sends the alarm floor, plus the floors directly above and below into evac, and all other floors into alert. If the system is not acknowledged in 5 minutes, the entire building goes into evac. A second stage keyswitch automatically evacuates the entire building.